Friday, April 7, 2017

Safety Tidbit 2.35 - Is a spray booth necessary?


Safety Tidbit 2.35 – Is a spray booth necessary?

                        OSHA Ventilation Standard (1910.94)
                        OSHA Spray Finishing of Flammable and Combustible materials 1910.107

A colleague recently asked me when is a booth necessary for spray painting operations? His example was that the employer periodically spray applies flammable paints (not aerosol cans) on signs and the back of large construction trucks. The operation lasts less than 15-20 minutes and uses a quart or less of paint at a time.

OSHA’s 1910.94(c)(2) states that spray booths or spray rooms are to be used to enclose or confine all spray finishing using organic or inorganic materials. Since the primary purpose of 1910.94(c) is to protect health, this is not a big deal if the appropriate PEL in Subpart Z of Part 1910 is not exceeded.

Therefore, if no OSHA PEL is exceeded during spray finishing operations, the operation falls under the OSHA standard at 1910.107. That standard does not have an enclosure provision like 1910.94(c) requiring that all spray finishing using flammable and combustible materials be confined to spray booths or spray rooms. However, the 1910.107(g)(1) requires that "[spraying shall not be conducted outside of predetermined spraying areas." Paragraph 1910.107(a)(2) defines a "spraying area" as "[any area in which dangerous quantities of flammable vapors or mists, or combustible residues, dusts, or deposits are present due to the operation of spraying processes." OSHA interprets "dangerous quantities of flammable vapors or mists" in 1910.107(a)(2), to be areas with concentrations exceeding 25% of the lower flammable limit (LFL) of any chemical used at any time during the spray finishing operations, without the benefit of ventilation required under the standard.

Example: To determine the lower explosive limits of the most common solvents used in spray finishing, see Table G-11 of 1910.94. Column 1 gives the number of cubic feet of vapor per gallon of solvent and column 2 gives the lower explosive limit (LEL) in percentage by volume of air. Note that the quantity of solvent will be diminished by the quantity of solids and nonflammables contained in the finish.

To determine the volume of air in cubic feet necessary to dilute the vapor from 1 gallon of solvent to 25 percent of the lower explosive limit, apply the following formula:

Dilution volume required per gallon of solvent =
4 X (100 - LEL) X (cubic feet of vapor per gallon) / LEL

Using toluene as the solvent.

1. LEL of toluene from Table G-11, column 2, is 1.4 percent.

2. Cubic feet of vapor per gallon from Table G-11, column 1, is 30.4 cubic feet per gallon.

3. Dilution volume required =
4 X (100 - 1.4) X 30.4 / 1.4 = 8,564 cubic feet/gallon.
4. To convert to cubic feet per minute of required ventilation, multiply the dilution volume required per gallon of solvent by the number of gallons of solvent evaporated per minute.

Therefore: If the operation uses one quart of paint over 15 minutes.
(0.25 gallons/15 minutes) = 0.0167gallons/minute or GPM
or in other words, one gallon will evaporate every approx. 60 minutes

5. 8,564 CF/gal X 0.0167 GPM = 143 CFM

However, 25 percent of the LEL or in our example above 1.4%/25 equals 0.056%. Converted to parts per million (PPM) is 0.056%X10,000=560 PPM. OSHA’s acceptable ceiling concentration for Toluene is 300 PPM and OSHA’s acceptable maximum peak above the acceptable ceiling concentration for an 8-hr shift is 500 PPM. All provided the total 8-hour time-weighted average stays below 200 PPM.

So back to the original question of whether a spray booth was necessary. More information is needed (SDS) and an industrial hygiene evaluation of the work area.

Hope this was helpful and thanks for reading my Safety Tidbits ~ Bryan

No comments:

Post a Comment